Work orders / WO-2026-01107
P2 WO-2026-01107
Corrective work order, Verified. At Ballard Yards Charging.
Response
- Priority
- P2, working-hours response (Mon–Fri 07:00–18:00 Pacific)
- Created
- Jun 10, 12:17 PDT
- Response due
- Jun 12, 14:16 PDT
- Planned
- Jun 11, 07:06 PDT
- On site
- Jun 11, 07:16 PDT
- Completed
- Jun 11, 09:47 PDT
- Verified
- Jun 11, 11:17 PDT
Who and where
- Site
- Ballard Yards Charging TW-SEA-011
- Technician
- Danielle Ortiz, Seattle
- Contact
- +1-206-555-0218, danielle.ortiz@example.com
- High voltage cert
- Yes, valid until Jan 15, 2027
- Charge points
- TW-SEA011-CP1
Notes
GroundFailure on TW-SEA011-CP1. Ground fault detected during pre-charge; sessions abort before power flows.
Faults answered
| Fault | Severity | Age | Charge point | Raised | Origin | Work order |
|---|---|---|---|---|---|---|
| FLT-26-0905
GroundFailure, Closed |
High | 164 d 3 h | – | Jun 10, 11:21 PDT | ChargePoint | No work order |
Service visits
Jun 11, 07:16 PDT to 09:47 PDT
Danielle Ortiz
- Findings
- Insulation resistance low on the output; the ground fault interrupter trips under load.
- Work done
- Replaced the ground fault interrupter module (RRE-GF-020); insulation test passed and three test sessions completed.
- Warranty claim
- VG-WC-26-0903
Parts fitted
| Part | Qty | Reason | From | Fitted |
|---|---|---|---|---|
| RRE-GF-020 Ground fault interrupter module | 1 | Repair | VanStock | Jun 11, 08:11 PDT |