P2 WO-2026-01120

Corrective work order, Verified. At Union Station Pacific Ave.

Response

Priority
P2, working-hours response (Mon–Fri 07:00–18:00 Pacific)
Created
Aug 19, 14:39 PDT
Response due
Aug 21, 16:38 PDT
Planned
Aug 20, 11:29 PDT
On site
Aug 20, 11:39 PDT
Completed
Aug 20, 14:36 PDT
Verified
Aug 20, 16:06 PDT

Who and where

Site
Union Station Pacific Ave TW-TAC-006
Technician
Megan O'Connell, Tacoma
Contact
+1-253-555-0305, megan.oconnell@example.com
High voltage cert
Yes, valid until Apr 12, 2027
Charge points
TW-TAC006-CP1

Notes

OverCurrentFailure on TW-TAC006-CP1. Output over-current trip at the start of a session.

Faults answered

FaultSeverityAgeCharge pointRaisedOriginWork order
FLT-26-0917
OverCurrentFailure, Closed
High 94 d 1 h–
Aug 19, 13:27 PDT ChargePoint No work order
FLT-26-0918
InternalError, Closed
Low 94 d 0 h–
Aug 19, 13:39 PDT ChargePoint No work order

Service visits

Aug 20, 11:39 PDT to 14:36 PDT Megan O'Connell
Findings
One power stage draws unbalanced current and trips the protection.
Work done
Replaced the breaker 3-pole 125A (RRE-BR-300); load test passed at rated current.
Warranty claim
VG-WC-26-0910

Parts fitted

PartQtyReasonFromFitted
RRE-BR-300
Breaker 3-pole 125A
1RepairVanStockAug 20, 12:34 PDT