Work orders / WO-2026-01106
P1 WO-2026-01106
Corrective work order, Verified. At Tacoma Dome Event Hub.
Response
- Priority
- P1, around-the-clock response
- Created
- Jun 2, 09:03 PDT
- Response due
- Jun 2, 13:03 PDT
- Planned
- Jun 2, 10:54 PDT
- On site
- Jun 2, 11:04 PDT
- Completed
- Jun 2, 13:18 PDT
- Verified
- Jun 2, 14:48 PDT
Who and where
- Site
- Tacoma Dome Event Hub TW-TAC-001
- Technician
- Megan O'Connell, Tacoma
- Contact
- +1-253-555-0305, megan.oconnell@example.com
- High voltage cert
- Yes, valid until Apr 12, 2027
- Charge points
- TW-TAC001-CP1
Notes
PowerSwitchFailure on TW-TAC001-CP1. Main contactor does not close; no output on any connector.
Faults answered
| Fault | Severity | Age | Charge point | Raised | Origin | Work order |
|---|---|---|---|---|---|---|
| FLT-26-0903
PowerSwitchFailure, Closed |
Critical | 172 d 6 h | – | Jun 2, 08:14 PDT | ChargePoint | No work order |
Service visits
Jun 2, 11:04 PDT to 13:18 PDT
Megan O'Connell
- Findings
- Main contactor contacts welded; coil resistance out of range.
- Work done
- Replaced the main power contactor 200A (VG-CT-4011); torque checked on the power terminals and a full-power session completed.
- Warranty claim
- VG-WC-26-0902
Parts fitted
| Part | Qty | Reason | From | Fitted |
|---|---|---|---|---|
| VG-CT-4011 Main power contactor 200A | 1 | Repair | VanStock | Jun 2, 11:59 PDT |