Work orders / WO-2026-01149
P3 WO-2026-01149
Corrective work order, Completed. At Freighthouse Square Lot.
Response
- Priority
- P3, working-hours response (Mon–Fri 07:00–18:00 Pacific)
- Created
- Nov 12, 11:05 PST
- Response due
- Nov 19, 11:05 PST
- Planned
- Nov 16, 09:00 PST
- On site
- Nov 16, 09:10 PST
- Completed
- Nov 16, 11:00 PST
- Verified
- –
Who and where
- Site
- Freighthouse Square Lot TW-TAC-005
- Technician
- Ryan Delgado, Tacoma
- Contact
- +1-253-555-0293, ryan.delgado@example.com
- High voltage cert
- Yes, valid until Feb 28, 2027
- Charge points
- TW-TAC005-CP1
Notes
HighTemperature on TW-TAC005-CP1. Cabinet temperature above the limit; output power derated.
Faults answered
| Fault | Severity | Age | Charge point | Raised | Origin | Work order |
|---|---|---|---|---|---|---|
| FLT-26-0947
HighTemperature |
Medium | 9 d 3 h | – | Nov 12, 10:20 PST | ChargePoint | No work order |
Service visits
Nov 16, 09:10 PST to 11:00 PST
Ryan Delgado
- Findings
- Cooling fan not spinning and the intake filter clogged with dust.
- Work done
- Cleaned the intake filter and freed the fan; cabinet temperature normal after thirty minutes at full load.
Parts fitted
No part fitted under this work order.