Work orders / WO-2026-01149

P3 WO-2026-01149

Corrective work order, Completed. At Freighthouse Square Lot.

Response

Priority
P3, working-hours response (Mon–Fri 07:00–18:00 Pacific)
Created
Nov 12, 11:05 PST
Response due
Nov 19, 11:05 PST
Planned
Nov 16, 09:00 PST
On site
Nov 16, 09:10 PST
Completed
Nov 16, 11:00 PST
Verified
–

Who and where

Site
Freighthouse Square Lot TW-TAC-005
Technician
Ryan Delgado, Tacoma
Contact
+1-253-555-0293, ryan.delgado@example.com
High voltage cert
Yes, valid until Feb 28, 2027
Charge points
TW-TAC005-CP1

Notes

HighTemperature on TW-TAC005-CP1. Cabinet temperature above the limit; output power derated.

Faults answered

FaultSeverityAgeCharge pointRaisedOriginWork order
FLT-26-0947
HighTemperature
Medium 9 d 3 h–
Nov 12, 10:20 PST ChargePoint No work order

Service visits

Nov 16, 09:10 PST to 11:00 PST Ryan Delgado
Findings
Cooling fan not spinning and the intake filter clogged with dust.
Work done
Cleaned the intake filter and freed the fan; cabinet temperature normal after thirty minutes at full load.

Parts fitted

No part fitted under this work order.